• Non Addressable Fire Alarm Smoke Detector, Smoke Sensor
  • Non Addressable Fire Alarm Smoke Detector, Smoke Sensor

Non Addressable Fire Alarm Smoke Detector, Smoke Sensor

Product Approval: UL521/UL268
Operating Voltage: DC(12/24/48)V
Sampling Time: <(3~5)S
Alarm Indicator: Dual Red LEDs
Remote LEDs Output Current(Max): 15mA
Reset Time: <5s
Samples:
US$ 10/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2012

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
SNC-300-S2
Transport Package
1/Box, 100PCS/CTN
Specification
dia. 102*45mm
Trademark
NUMENS
Origin
Ningbo, China
HS Code
8531100000
Production Capacity
200, 000 PCS/Month

Product Description

SNC-300 non-addressable photoelectric smoke detectors are state-of-the-art detectors suitable for connection to 2-wire or 4-wire non-addressable fire detection control and indicating equipment, or to addressable fire detection control and indicating equipment that can accept non-addressable type detectors.
Advanced electronics in conjunction with a photoelectric smoke sensing chamber provide early detection of fire and high immunity against unwanted alarms.

 

Features:

·    Photoelectric smoke sensor
·    Analogue detection discrimination
·    Dual LEDs for 360° visibility
·    2-wire and 4-wire models for DC 12 V and DC 24 V operation
·    4-wire model for DC 48 V operation
·    4-wire models available with a N/O alarm relay output
·    4-wire models available with auto-reset
·    2-wire models available with remote LED output
·    Connects to zone monitor for use with addressable control and indicating equipment

Specification:

 
Operating voltage DC (12/24/48) V
Start-up current ≤ 135 µA
Start-up time ≤ 30 s
Quiescent current ≤ 75 µA
Sampling time (3 ~ 5) s
Alarm indicator Dual red LEDs
Remote LED output current (max) 15 mA
Reset voltage ≤ 1 V
Reset time ≤ 5 s
Alarm response threshold (0.08 ~ 0.15) dB/m
Alarm output relay SPST. N/O
Operating temperature (-10 ~ +55) °C
Operating humidity (0 ~ 95) % RH, non-condensing
Dimensions (excluding contacts) Φ 102 mm × 45 mm


Ordering Information: 
Part Number 2-wire 4-wire Remote Indicator Relay Output Auto-Reset
SNC-300-S2 a - - - -
SNC-300-SL a - - -
SNC-300-SR a - - -
SNC-300-SRR a - - - -
SNC-300-SR4 - - -
SNC-300-S2-U b - - - -
SNC-300-SL-U b - - -
SNC-300-SR-U b - - -
SNC-300-SA - - -

Non Addressable Fire Alarm Smoke Detector, Smoke Sensor

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2012

Suppliers with verified business licenses

Manufacturer/Factory
Year of Establishment
2011-07-06
Management System Certification
ISO9001:2008