Type: | Smoke Alarm |
---|---|
Signal Transmission: | Wired Alarm |
Working Mode: | Active |
Certification: | ISO, UL268 En54-5, En54-7 |
Application: | Indoor |
Working Principle: | Electro-Optical Type |
Customization: |
---|
Suppliers with verified business licenses
Description
SNA-360 analogue addressable photoelectric smoke detectors are microprocessor controlled state-of-the-art detectors compatible with popular control and indicating equipment loop protocols.
Advanced electronics in conjunction with a photoelectric smoke sensing chamber provides early detection of fire and high immunity against unwanted alarms.
Features
Specifications
Operating voltage | DC (17 ~ 28) V |
Start-up current | ≤ 400 µA |
Start-up time | ≤ 30 s |
Quiescent current | ≤ 260 µA |
Sampling time | ≤ 2 s |
Alarm response threshold | (0.08 ~ 0.15) dB/m |
Alarm indicator | Dual red LEDs |
Remote LED output current (max) | 2 mA |
Reset voltage | ≤ 3 V |
Reset time | ≤ 30 s |
Usable addresses per alarm loop | 125 |
Operating temperature | (-10 ~ +55) °C |
Operating humidity | (0 ~ 95) % RH, non-condensing |
Dimensions (excluding contacts) | Φ 102 mm × 34 mm |
Part Number | Remote Indicator |
SNA-360-S2 | - |
SNA-360-SL | √ |
Suppliers with verified business licenses