• Separate Indicator for Quiescent, Alarm, Fault, Input/Output Module (621-002)
  • Separate Indicator for Quiescent, Alarm, Fault, Input/Output Module (621-002)

Separate Indicator for Quiescent, Alarm, Fault, Input/Output Module (621-002)

Type: Smoke Alarm
Signal Transmission: Wired Alarm
Working Mode: Active
Certification: CE, ISO
Application: Indoor
Working Principle: Electro-Optical Type
Samples:
US$ 20/Piece 1 Piece(Min.Order)
| Request Sample
Customization:

Contact Supplier

Gold Member Since 2012

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
621-002
Transmission Mode
Cable
Operating Voltage
DC(17~30)V
Input Voltage(Pulsed)
DC(5~9)V
Sampling Time
1s
Usable Addresses Per Alarm Loop
125
Transport Package
1/Box, 100PCS/CTN
Specification
95*95*42mm
Trademark
Numens
Origin
Ningbo, China
HS Code
8531100000
Production Capacity
50, 000PCS/Month

Product Description

621 analogue addressable single input/output modules provide the interface to connect an electrically isolated dry-contact switched input to Numens 2-wire addressable fire detection control and indicating equipment.
A parallel resistive input filter allows multiple states to be monitored at the input. The states are converted to the loop communications protocol by the module, to enable them to be displayed on the control and indicating equipment.

Features:

·    Single voltage-free relay output
·    Output relay can be powered internally or externally (selectable at installation)
·    Single input for connection to dry contact inputs
·    Monitors and signals three distinct input states: Normal; Alarm; Open-circuit
·    Separate indicators for Quiescent, Alarm and Fault conditions
·    Polling indicator shows quiescent operation
·    DC 24 V operation
·    DIP switch address setting
·    125 usable detector address settings per loop 

Specification:
operating voltage DC(17~30)V
quiescent current ≤400μA
input voltage(pulsed) DC(5~9)V
sampling time 1s
resistance for input short-circuit conditon ≤2k2Ω
resistance for input alarm conditon (2k2~8k2)Ω
resistance for input quiescent conditon (8k2~47k)Ω
resistance for input open-circuit conditon ≥47Ω

FAQ:
Q1:Are you a manufacturer or trading company?
A1:Numens is a professional fire alarm system manufacturer.
 
Q2:What kind of production service do you provide?
A2:The whole fire alarm system,include Addressable system, Conventional system, Residential system and so on....
 
Q3:What kind of certification do you have?
A3:Numens was EN,BSI,UL,SGS certified and all the products were produced under these major international standard .
 
Q4:What is the lead time for new order?
A4:The lead time for new order is 25 days after confirm order.
 
Q5:How do I get price information?
A5:Sales representatives are responsible for providing detailed price information within 1 workday after get your inquiry.

Separate Indicator for Quiescent, Alarm, Fault, Input/Output Module (621-002)
Separate Indicator for Quiescent, Alarm, Fault, Input/Output Module (621-002)
 

Send your message to this supplier

*From:
*To:
avatar Ms. sandy
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Contact Supplier

Gold Member Since 2012

Suppliers with verified business licenses

Manufacturer/Factory
Year of Establishment
2011-07-06
Management System Certification
ISO9001:2008